33KV Transformer
33KV 11KV Transformer
Step Down Transformer 33KV To 11KV
Power Transformer 33KV 11KV
33/11 KV Power Transformer
33KV To 11KV Transformer
33/11KV Transformer
Step Up Transformer 11KV To 33KV
11KV To 33KV Transformer
Features
Baoding Zhongyi Electric Corporation is one of the leading manufacturers and suppliers of 33kv transformer in China, featured by quality products and good price. Please rest assured to buy advanced 33kv transformer for sale here from our factory.
A 33 kV transformer sits on the boundary between transmission and distribution. On one side is the 33 kV network that utilities and large industrial estates run; on the other is whatever your plant actually consumes - 11 kV for onward site distribution, 6.6 kV for older networks and mining, or 400 V if the site is fed directly. Which of those you need is the single decision that shapes everything else about the unit, including its cost.
We build the 33KV Transformer in two-winding, oil-immersed form from 630 kVA to 31,500 kVA at our works in Baoding, Hebei, with copper windings and ONAN or ONAF cooling. This page is an overview of the whole range: the ratings, the losses and impedance that apply to each, the voltage combinations we build most often, and what we need from you in order to quote one.

Oil-immersed units in the assembly bay before dispatch
Ratings, losses and impedance
The table below is the core of this page. Impedance rises in steps as the rating climbs, and the vector group changes once you pass 10,000 kVA. Neither is a manufacturing quirk, and it is worth understanding both before you specify.
Common electrical specification
- Rated high voltage: 33 kV / 34.5 kV / 35 kV / 38.5 kV
- Rated low voltage: 3.15 kV / 6.3 kV / 6.6 kV / 10.5 kV / 11 kV / 11.5 kV
- Vector group: Yd11 up to 10,000 kVA, Ynd11 from 12,500 kVA
- Winding material: copper
- Cooling: ONAN / ONAF
- Frequency: 50 Hz / 60 Hz
- Ambient temperature: −10 °C to +40 °C
- Altitude: up to 1,000 m above sea level
|
Rating (kVA) |
No-load loss (kW) |
No-load current (%) |
Impedance voltage |
|---|---|---|---|
|
630 |
1.04 |
1.10 |
6.5 % |
|
800 |
1.23 |
1.00 |
6.5 % |
|
1,000 |
1.44 |
1.00 |
6.5 % |
|
1,250 |
1.76 |
0.90 |
6.5 % |
|
1,600 |
2.12 |
0.80 |
6.5 % |
|
2,000 |
2.72 |
0.70 |
6.5 % |
|
2,500 |
3.20 |
0.60 |
6.5 % |
|
3,150 |
3.80 |
0.56 |
7.0 % |
|
4,000 |
4.52 |
0.56 |
7.0 % |
|
5,000 |
5.40 |
0.48 |
7.0 % |
|
6,300 |
6.56 |
0.48 |
7.5 % |
|
8,000 |
9.00 |
0.42 |
7.5 % |
|
10,000 |
10.88 |
0.42 |
7.5 % |
|
12,500 |
12.60 |
0.40 |
8.0 % |
|
16,000 |
15.20 |
0.40 |
8.0 % |
|
20,000 |
18.00 |
0.40 |
8.0 % |
|
25,000 |
21.28 |
0.32 |
8.0 % |
|
31,500 |
25.28 |
0.32 |
8.0 % |
No-load loss and no-load current are listed per rating because they are the two figures you can evaluate against a tender without waiting for a drawing - no-load loss runs twenty-four hours a day for the life of the unit, whether the plant is producing or not. Load loss is fixed per order and confirmed by the impedance-voltage and load-loss measurements on the routine test report. We do not publish one figure for it because it moves with the copper design and with the impedance you choose.
Why impedance rises with rating
Read down the impedance column and the pattern looks backwards: bigger transformers quote higher impedance, not lower. It is not a limitation of the winding shop. Impedance is what limits the fault current the downstream breaker has to interrupt, and the fault current rises with rating as well - so impedance has to rise with it, or the low-voltage switchgear would have to be specified to a fault level nobody wants to pay for.
Two worked examples make it concrete, both on an 11 kV secondary. A 630 kVA unit carries 33 A at 11 kV; at 6.5 % impedance that is roughly 510 A of fault current on the LV side. Step up to 10,000 kVA and the LV current is 525 A, but at 7.5 % impedance the fault current is about 7 kA - roughly fourteen times higher, because the rise in rating more than offsets the rise in impedance.
The practical consequence is simple. If you uprate a transformer later without re-checking the breaker on the LV board, that is how boards get destroyed. Send us the breaking capacity of the switchgear you intend to use and we will confirm the impedance sits comfortably inside it, or tell you that the board needs to change.
33/11 kV, 33/6.6 kV, or straight to 400 V
Three combinations cover almost everything we ship in this class, and the choice is usually made by what already exists on site rather than by preference.
33/11 kV is the standard arrangement where the site runs its own 11 kV distribution, and it is the most common enquiry we receive at this voltage class. The low-voltage current stays modest - a 2,000 kVA unit carries 105 A at 11 kV - so the cable, CTs and switchgear on that side remain small and inexpensive. If you intend to distribute at 11 kV across a site, start here.
33/6.6 kV turns up where the existing network is already 6.6 kV: older plants, and a large share of mining installations. A 2,000 kVA unit carries about 175 A at 6.6 kV.
33/0.4 kV feeds the low-voltage board directly, with no intermediate distribution. It removes a switchroom and a set of cables, and it puts the entire load through a single LV board: a 2,000 kVA unit delivers 2,887 A at 400 V. That is a serious busbar, and it is why most sites above roughly 1,000 kVA keep an 11 kV stage in between.
If you are not sure which of the three your site should use, describe what the transformer feeds and how far the load has to run, and we will tell you which arrangement we would pick and why.

Custom build with side outgoing lines, made to a customer's drawing
ONAN or ONAF
ONAN is the base rating: the oil circulates by natural convection and the tank surface does the radiating. You pay for that tank once, and it needs no maintenance for the life of the unit. ONAF adds fans and forced air across the radiators, which releases roughly 25 % to 33 % more capacity from the same core and coils.
Which one you need depends on your load shape rather than your nameplate. A steady base load with occasional peaks will normally sit inside the natural overload capability of an ONAN unit. If you expect to run near nameplate for hours at a time in a hot climate, specify the tank ONAF-capable and run it ONAN until you actually need the fans. It costs a little more at the outset and saves you from buying a larger transformer that then sits at 40 % load for the rest of its life.
Note the +40 °C ambient ceiling in the specification above. Above that temperature, or above 1,000 m altitude, the nameplate rating has to be corrected under IEC 60076-2. Mention the site conditions when you enquire - correcting it after the design is fixed means either a de-rated unit or a second cooling stage.
Standards, testing and documentation
Every 33KV Transformer we build is designed and tested to IEC 60076, and we work to IS or BS where a project specifies them. Each unit ships with a routine test report covering winding resistance, ratio and vector group, no-load loss and no-load current, impedance voltage and load loss, applied voltage and induced voltage. Lightning impulse, temperature rise, short-circuit and noise measurements are available as type tests, with third-party witnessing through your nominated inspection body if the contract calls for it.
Documentation with each shipment includes the routine test report, the approved outline drawing and the nameplate record, plus CE, UL and RoHS declarations where they are required. ISO 9001:2015 covers the process.

Quality management, CE conformity and product certification held by the works
Inspection is welcome. We can arrange third-party witness testing, and we are happy to host a factory visit or a pre-shipment inspection at any point in the order - ask and we will put the dates in the contract rather than leaving them to goodwill.
Manufacturing, packing and shipping
Our site covers 33,300 m² with 260 employees and an annual capacity above 1,000 MVA; eighteen engineers handle design and type-test work. Cores are step-lapped from cold-rolled grain-oriented silicon steel, windings are copper and vacuum-dried before oil filling, and every tank is welded, pressure-tested, filled and leak-tested before it leaves the bay.

Coil winding, vacuum drying and high-voltage testing, all in-house
Standard export packing is a seaworthy wooden crate with the transformer braced to the base plate, and pallets or rack frames where the site has a crane limit. For the larger ratings the shipping and lifting arrangements are agreed per order, because they depend on the transport route and on what the crane at site can actually pick up. Send us the destination port and the lifting capacity available and we will confirm the packing and the heaviest single piece.

Export packing: braced to the base, then closed in a seaworthy case
MOQ is one unit. Lead time is quoted per order - for a rating we already build it is measured in weeks rather than months. Warranty is 24 months. OEM and ODM are available, including your nameplate, your drawing numbers and your test report format.
FAQ
Why do we use a 33/11 kV transformer?
Because 33 kV is economical to move over distance and 11 kV is manageable to distribute on site. Stepping down to 11 kV at the boundary lets you run a site-wide distribution network with ordinary cable and switchgear, instead of taking 33 kV into every building. It is the arrangement most utilities and large industrial estates already use, which is also why the spares and the protection practice are well understood locally.
What is the difference between a 33 kV and an 11 kV transformer?
The voltage class they are insulated for, and everything that follows from it. A 33 kV unit has a longer creepage path, larger clearances, bigger bushings, more oil and a heavier tank, so it costs more and takes more space for the same kVA. The current is also lower for the same rating: 2,000 kVA carries 35 A at 33 kV but 105 A at 11 kV. If your incoming supply is 33 kV, you need a 33 kV winding on that side regardless of what you distribute at.
How do I know which rating to ask for?
Send the load list, or even a summary of it - connected load, the largest motor, and whether any of it runs continuously. Our rule of thumb is a continuous load of 60 % to 75 % of nameplate, so that a cooling fault or a single outage does not take the plant down. Working that backwards gives you the rating. You do not need to have this figured out before contacting us; it is often the first thing we do together.
Can you build to IS or BS instead of IEC, and can I arrange third-party inspection?
Yes to both. Tell us the standard and the inspection body in your enquiry and we will confirm the test schedule in the offer rather than at the end of manufacturing. Witness testing and pre-shipment inspection are routine for us, not an exception.
How long before I have a price?
Our team answers enquiries within 24 hours, and a priced offer usually follows within a day or two of that if the specification is clear. If you are still weighing 33/11 kV against 33/0.4 kV, or a 2,500 kVA unit against 3,150 kVA, say so in the first message - we will quote the options side by side, which is faster than two rounds of questions.
Get a quotation
Nine items and we can quote without another round of emails:
- Rated power, or the load you need to carry
- Primary voltage, and whether it is 33 kV, 34.5 kV, 35 kV or 38.5 kV
- Secondary voltage, and whether the neutral is brought out
- Vector group, if your specification fixes it
- Impedance, or the fault level your switchgear is rated for
- Loss limits, or your loss capitalisation formula
- Indoor or outdoor, and the clearances available on site
- Site ambient temperature, altitude and seismic zone
- Applicable standard, and any third-party inspection requirement
A 33KV Transformer is sized to your fault level, your secondary voltage and your load profile, not against a list price, so those three matter more than anything else you can tell us. Send them even as rough numbers, and you will get a priced offer together with a preliminary outline drawing. If you would rather just describe the project in a paragraph and let us ask the rest, that works too - a good number of our orders start that way.
Baoding Zhongyi Electric Corporation · MOQ 1 unit · 24-month warranty · 7×24 technical support · Send your specification and we will come back with a price · WhatsApp +86 135 1322 2010 · gracejia@zydqjt.com