1500 KVA Cast Resin Transformer
Voltage: 10-33 kV
Power rating: 1500 KVA
Frequency: 50 Hz
Cooling Method: AN or AF
Windings: Copper or Aluminum
Material: Resin Cast
Features
Baoding Zhongyi Electric Corporation is one of the leading manufacturers and suppliers of 1500 kva cast resin transformer in China, featured by quality products and good price. Please rest assured to buy advanced 1500 kva cast resin transformer for sale here from our factory.
A cast resin transformer is specified for what it does not have. There is no oil in it, which means no bund, no oil-retention pit under the plinth, no top-up on the maintenance schedule and no dissolved-gas analysis every year. It also means no oil to spill, and nothing in the unit that will feed a fire. That is why the enquiry almost always comes from a building rather than a yard: a basement, a tunnel, a hospital plant room, a shopping centre, the core of a high-rise.
The 1500 KVA Cast Resin Transformer on this page is a three-phase dry-type unit with cast-resin insulated windings, built at our works in Baoding, Hebei, for high voltages from 10 kV to 33 kV. It is the rating that turns up most often in medium commercial and light industrial work - big enough to carry a whole building, small enough to sit in a room that was designed for something else.
Where cast resin is the only option
An oil-immersed unit needs containment: a bunded plinth, oil retention, and fire separation from anything occupied. Where those cannot be provided, the decision is not really a preference between two products - it is that one of them is not permitted.
That covers more places than most specifications admit:
- Basements and below-ground plant rooms, where there is no route for an oil spill to go and no way to drain one
- Tunnels and underground stations, where a fire load is not a theoretical concern
- Hospitals, shopping centres and office cores, where the substation sits inside an occupied building
- High-rise buildings, where the electrical room is often too small for an oil-filled unit of the same rating
- Wind, solar and water-treatment sites, where an oil spill reaches something that matters
- Any site whose fire engineer has already ruled out an oil-filled transformer
Cast resin windings are flame-retardant and self-extinguishing, and the fire load they carry is a fraction of an oil-filled unit of the same rating. In practice that is what buys the reduced fire separation, and it is usually the point at which the higher price per kVA stops looking expensive.
The trade-offs are real, and worth stating plainly. Cast resin costs more per kVA than an oil-filled unit at this rating, and it is physically larger for the same capacity. It also dislikes damp, dust and salt, so if the room is not clean and dry the unit needs a protected enclosure rather than being installed bare. If none of the fire or containment constraints apply to your site, an oil-filled unit is usually the cheaper answer and we will say so.
Ratings and the design range
The table below describes the range we design in for this rating. It is deliberately a range rather than a fixed specification: the figures for your unit are fixed on the approved outline drawing, and every electrical figure is then confirmed by measurement on the routine test report. If your project fixes any of these values, tell us and we will design to yours.
|
Rated power |
1,500 kVA |
|
High voltage |
10 kV / 11 kV / 15 kV / 20 kV / 22 kV / 33 kV |
|
Low voltage |
0.4 kV / 0.415 kV / 0.433 kV, or 6.6 kV / 11 kV where the site distributes at medium voltage |
|
Impedance voltage |
6 % typical, designed in the 6 % to 8 % band |
|
Insulation class |
Class F as standard; Class H available for higher ambient or sustained overload duty |
|
Cooling |
AN (natural air) standard; AF (forced air, fans) available |
|
Protection degree |
IP00 / IP20 for a clean indoor cubicle; IP23 where the room is dusty or damp |
|
Winding material |
Copper as standard; aluminium on request |
|
Frequency |
50 Hz / 60 Hz |
|
Vector group |
Dyn11 typical, others to specification |
|
Standard |
IEC 60076-11 for dry-type units, with IEC 60076-1; IS and BS on request |
Currents follow the usual relationship, I = S / (√3 × V). At 1,500 kVA the high-voltage current is 86.6 A on a 10 kV winding and 78.7 A on 11 kV - small enough that the cable and switchgear on that side are governed by the system fault level rather than by load. The low-voltage figure is the one that drives cost: 2,165 A at 400 V. State the secondary voltage in your enquiry, because 400 V and 415 V are not interchangeable in a busbar calculation.
Impedance, and what it does to your LV board
Impedance is the number that connects this transformer to the cost of everything downstream of it, and it is worth settling before the switchgear is ordered rather than after.
At 1,500 kVA with a 400 V secondary the rated LV current is 2,165 A. Design the unit at 6 % impedance and a solid short circuit at that busbar produces roughly 36 kA. Design the same transformer at 8 % and the figure falls to about 27 kA. That difference is the difference between a 36 kA and a 40 kA breaker frame, and it can be the difference between one switchgear package and the next one up.
There is a cost on the other side too: a higher impedance means slightly higher load loss and slightly worse voltage regulation at full load. Neither answer is automatically right. Send us the breaking capacity of the LV board you intend to use, or the impedance your specification fixes, and we will design to it and confirm the fault level in writing.
AN or AF
AN is the base rating: the unit dissipates its heat to the room by natural convection and radiation, with nothing to maintain and nothing to fail. AF adds fans and forced air across the windings, which on a dry-type unit releases commonly around 40 % more capacity from the same core and coils.
Two things decide it. If your peak load is short and your base load is well under nameplate, AN alone is normally sufficient and cheaper to own. If you expect to run near nameplate for hours at a time, order the unit AF-rated and run it on AN until you need the fans - the fan bank and the control wiring have to be designed in from the start, so this is an enquiry-stage decision, not a site modification.
Note also that fans introduce moving parts and a maintenance item that a pure AN unit does not have. Present the fans as an option to your maintenance team rather than as a default.
What cast resin changes about the room
Removing the oil changes the building, not just the equipment. There is no bund to construct and no oil-retention pit, which is often what makes a below-ground substation possible at all. There is no oil top-up, no oil sampling and no dissolved-gas analysis on the maintenance schedule - the annual routine becomes an inspection of the windings, the connections and the fans rather than a fluid programme.
The one thing that catches people out is ventilation. Oil carries heat to the tank surface, and the tank can be large; in a cast resin unit all of the heat leaves through the air, and the windings are only as good as the air moving past them. A sealed plant room will de-rate this transformer. Plan the intake and exhaust openings, or the mechanical ventilation, before the room is built - correcting it afterwards usually means accepting a lower usable rating or adding fan cooling you did not want.
Clearances and protection degree are the other two decisions. A clean plant room suits a bare IP00 or IP20 unit in a cubicle; a basement car park, a dusty workshop or a coastal site calls for IP23 or an enclosure. If you send us the room - dimensions, what is above it, and where the air comes from - we will tell you what we would specify and what we would not.

Cast-resin windings, clamp frame and HV terminals on a completed unit
Standards, testing and documentation
Every 1500 KVA Cast Resin Transformer is designed and tested to IEC 60076-11, the dry-type standard, with IEC 60076-1 alongside it; we work to IS or BS where a project specifies them. Routine testing covers winding resistance, ratio and vector group, no-load loss and no-load current, impedance voltage and load loss, applied voltage and induced voltage.
One test matters more on a cast resin unit than on an oil-filled one: partial discharge measurement. A void or a poor bond inside the cast resin will not announce itself as a leak or a smell - it shows up as partial discharge, and it is the reason PD measurement is part of the routine schedule for dry-type windings rather than an optional extra. Ask for the PD figures with the test report, not just a pass certificate.
Dry-type units also carry environmental, climatic and fire-behaviour classifications under IEC 60076-11, covering humidity, condensation and how the unit behaves in a fire. Tell us which classification your specification calls for and we will confirm we can meet it before quoting, rather than discovering the gap at type-test stage.

Quality management, CE conformity and product certification held by the works
Documentation with each shipment includes the routine test report, the approved outline drawing, the nameplate record and the partial discharge results, plus CE, UL and RoHS declarations where they are required. ISO 9001:2015 covers the process. Third-party witness testing and pre-shipment inspection are routine for us, and a factory visit can be arranged at any point in the order.
Manufacturing, packing and shipping
Our site covers 33,300 m² with 260 employees and an annual capacity above 1,000 MVA; eighteen engineers handle design and type-test work. High-voltage windings are sectional, vacuum-cast, double glass-fibre covered coils; low-voltage windings are wound from copper foil. Cores are step-lapped from cold-rolled grain-oriented silicon steel, and resilient pads between core and clamp break the mechanical path that would otherwise carry vibration into the room as noise.

Cast-resin coils and a laminated core in assembly
Standard export packing is a seaworthy wooden crate with the unit braced to the base plate, and pallets or rack frames where the site has a crane limit. Each unit is fitted with a trolley whose wheels turn through 90 degrees, so it can be moved in either direction along a plant room without a bespoke skidding arrangement.

Export packing: braced to the base, then closed in a seaworthy case
MOQ is one unit. Lead time is quoted per order - for a rating we already build it is measured in weeks rather than months. Warranty is 24 months. OEM and ODM are available, including your nameplate, your drawing numbers and your test report format.
FAQ
Why choose a cast resin transformer instead of an oil-immersed one?
Because your site cannot have oil in it. If there is no room for a bund, no route for a spill, or the substation sits inside an occupied building, the oil-filled option is not available to you and the cost comparison never happens. Where those constraints do not apply, an oil-filled unit is cheaper per kVA and often smaller, and we build both - so we will tell you if you are paying for a dry-type unit you do not need.
Can it be installed in a basement, a tunnel or an occupied building?
Yes, and that is what this unit is for. Cast-resin windings are flame-retardant and self-extinguishing, there is no oil to spill or to feed a fire, and the fire load is a fraction of an oil-filled unit of the same rating. What the room still needs is ventilation and an appropriate protection degree, not containment. Local fire codes vary, so confirm the separation your authority requires - we will supply whatever documentation your fire engineer asks for.
What room does it need?
Two things matter more than floor area: air, and access. All of the heat leaves through the air, so a sealed room will de-rate the unit - plan intake and exhaust openings or mechanical ventilation before the room is built. For access, tell us the doorway width and the crane or forklift available and we will confirm the transport arrangement; the trolley fitted to the base lets the unit be moved in either direction once it is in.
Can you match the SCB-series specification I already have?
Yes. On 10 kV networks in Asia these units are usually ordered under SCB-series designations, and if your previous order, your specification or your consultant's drawing says SCB10 or SCB13, send it across - we will match the ratings, the impedance and the enclosure and confirm any deviation rather than quietly substituting something close.
How quickly will I get a price?
Our team answers enquiries within 24 hours and a priced offer usually follows within a day or two, if the specification is clear. If you are still deciding between 1,500 kVA and 2,000 kVA, or between IP20 and IP23, say so in the first message and we will price the options side by side - that is faster than two rounds of questions, and it usually makes the decision obvious.
Get a quotation
Nine items and we can quote without another round of emails:
- Rated power, or the load you need to carry
- High voltage - 10, 11, 15, 20, 22 or 33 kV
- Low voltage, and whether the neutral is brought out
- Vector group, if your specification fixes it
- Impedance, or the fault level your LV switchgear is rated for
- AN rating required, and whether you also want the AF rating
- Indoor or outdoor, and the protection degree required
- Room conditions: ambient, ventilation available, humidity or dust, altitude
- Applicable standard, insulation class, and any third-party inspection requirement
A 1500 KVA Cast Resin Transformer is sized to your fault level, your secondary voltage and the room it has to live in, not against a list price - so those three matter more than anything else you can tell us. Send them even as rough numbers and you will get a priced offer with a preliminary outline drawing. If you would rather just describe the project in a paragraph, that works too; a fair number of our orders start exactly that way.