Jsm Scb10 1600kVA Dry Type Transformers Distribution Transformer

Jsm Scb10 1600kVA Dry Type Transformers Distribution Transformer
Type:3 Phase Dry type Transformer
MOQ:1pc
Warranty:1 year
OEM/ODM Service:Yes
Certification:ISO 9001
Shipping:Sea
Payment:T/T
Features
Products Description
Specification
Model and Meaning
Technical Parameter for 6kV, 10kV& 30kVA-2500kVA With Off Circuit Dry Type Transformer
| (KVA)Rated capacity | Voltage Combination | Connection Group Symbol | No-load Loss(W) | Load Loss (W) | No-load Current (%) | Short-circuit Impedance(%) | ||||
| High Voltage (KV) | Tapping ranges of High Voltage | Low Voltage(KV) | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
| 30 | 6 6.3 6.6 10 10.5 11 | ±2.5% ±5% | 0.4 | Dyn11 Yyn0 | 190 | 670 | 710 | 760 | 2 | 4 |
| 50 | 270 | 940 | 1000 | 1070 | 2 | |||||
| 80 | 370 | 1290 | 1380 | 1480 | 1.5 | |||||
| 100 | 400 | 1480 | 1570 | 1690 | 1.5 | |||||
| 125 | 470 | 1740 | 1850 | 1980 | 1.3 | |||||
| 160 | 540 | 2000 | 2130 | 2280 | 1.3 | |||||
| 200 | ±2X2.5% ±5% | 620 | 2370 | 2530 | 2710 | 1.1 | ||||
| 250 | 720 | 2590 | 2760 | 2960 | 1.1 | |||||
| 315 | 880 | 3270 | 3470 | 3730 | 1 | |||||
| 400 | 980 | 3750 | 3990 | 4280 | 1 | |||||
| 500 | 1150 | 4590 | 4880 | 5230 | 1 | |||||
| 630 | 1340 | 5530 | 5880 | 6290 | 0.85 | |||||
| 630 | 1300 | 5610 | 5960 | 6400 | 0.85 | 6 | ||||
| 800 | 1520 | 6550 | 6960 | 7460 | 0.85 | |||||
| 1000 | 1770 | 7650 | 8130 | 8760 | 0.85 | |||||
| 1250 | 2090 | 9100 | 9690 | 10300 | 0.85 | |||||
| 1600 | 2450 | 11000 | 11700 | 12500 | 0.85 | |||||
| 2000 | 3050 | 13600 | 14400 | 15500 | 0.7 | |||||
| 2500 | 3600 | 16100 | 17100 | 18400 | 0.7 | |||||
| 1600 | 2450 | 1220 | 12900 | 13900 | 0.85 | 8 | ||||
| 2000 | 3050 | 15000 | 15900 | 17100 | 0.7 | |||||
| 2500 | 3600 | 17700 | 18800 | 20200 | 0.7 | |||||
Technical Parameter for 20kV & 50kVA-2500kVA With Off Circuit Dry Type Transformer
| (KVA)Rated capacity | Voltage Combination | Connection Group Symbol | No-load Loss(W) | Load Loss (W) | No-load Current (%) | Short-circuit Impedance(%) | ||||
| High Voltage (KV) | Tapping ranges of High Voltage | Low Voltage(KV) | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
| 50 | 20 22 24 | ±2.5% ±5% | 0.4 | Dyn11 Yyn0 | 340 | 1160 | 1230 | 1310 | 2 | 5.0 |
| 100 | 540 | 1870 | 1990 | 2130 | 1.8 | |||||
| 160 | 670 | 2350 | 2470 | 3460 | 1.8 | |||||
| 200 | ±2X2.5% ±5% | 730 | 2770 | 2940 | 3140 | 1.8 | ||||
| 250 | 840 | 3220 | 3420 | 3660 | 1.8 | |||||
| 315 | 970 | 3850 | 4080 | 4360 | 1.8 | |||||
| 400 | 1150 | 4650 | 4840 | 5180 | 1.1 | |||||
| 500 | 1350 | 5460 | 5790 | 6190 | 1.1 | |||||
| 630 | 1530 | 6450 | 6840 | 7320 | 1 | |||||
| 800 | 1750 | 7790 | 8260 | 8840 | 1 | |||||
| 1000 | 2070 | 9220 | 9780 | 10400 | 0.85 | |||||
| 1250 | 2380 | 10800 | 11500 | 12300 | 0.85 | |||||
| 1600 | 2790 | 13000 | 13800 | 14800 | 0.85 | |||||
| 2000 | 3240 | 15400 | 16300 | 17500 | 0.7 | 8.0 | ||||
| 2500 | 3870 | 18200 | 19300 | 20700 | 0.7 | |||||
| 2000 | 3240 | 16800 | 17800 | 19100 | 0.7 | |||||
| 2500 | 3870 | 20000 | 21200 | 22700 | 0.7 | |||||
Technical Parameter for 35kV & 50kVA-2500kVA With Off Circuit Dry Type Transformer
| (KVA)Rated capacity | Voltage Combination | Connection Group Symbol | No-load Loss(W) | Load Loss (W) | No-load Current (%) | Short-circuit Impedance(%) | ||||
| High Voltage (KV) | Tapping ranges of High Voltage | Low Voltage(KV) | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
| 50 | 35 36 37 38.5 | ±2.5% ±5% | 0.4 | Dyn11 Yyn0 | 450 | 1340 | 1420 | 1520 | 2.3 | 6 |
| 100 | 630 | 1970 | 2090 | 2230 | 2 | |||||
| 160 | 0.79 | 2650 | 2810 | 3000 | 1.5 | |||||
| 200 | ±2X2.5% ±5% | 0.88 | 3130 | 3320 | 3550 | 1.5 | ||||
| 250 | 0.99 | 3580 | 3800 | 4060 | 1.3 | |||||
| 315 | 1170 | 4250 | 4510 | 4820 | 1.3 | |||||
| 400 | 1370 | 5100 | 5410 | 5790 | 1.1 | |||||
| 500 | 1520 | 6270 | 6650 | 7110 | 1.1 | |||||
| 630 | 1860 | 7250 | 7690 | 8230 | 1 | |||||
| 800 | 2160 | 8600 | 9120 | 9760 | 1 | |||||
| 1000 | 2430 | 9860 | 10400 | 11100 | 0.75 | |||||
| 1250 | 2830 | 12000 | 12700 | 13600 | 0.75 | |||||
| 1600 | 3240 | 14600 | 15400 | 16500 | 0.75 | |||||
| 2000 | 3820 | 17200 | 18200 | 19500 | 0.75 | |||||
| 2500 | 4450 | 20600 | 21800 | 23300 | 0.75 | |||||


Production Process


Packing & Delivery
Generally, we will use wooden packing suitable for long distance transportation such as sea transportation.We can also customize special packaging according to customer requirements.
Why Choose Us



Hot Tags: 3 phase dry type distribution transformer, China, suppliers, manufacturers, factory, buy, price, for sale, single transformer, dual voltage transformers, cast resin transformer, single pole mounted transformer, mount transformer, 300kva dry type transformer
China Supply 10kv 2000 kVA 3 Phase Cast Resin Electrical Distribution Dry Type Transformer
No Information
You Might Also Like
Send Inquiry