3500 KVA Dry Type Transformer
video
3500 KVA Dry Type Transformer

3500 KVA Dry Type Transformer

Input Voltage: Up to 35kV
Output Voltage: Up to 11kV
Frequency: 50/60Hz
Cooling: AN/AF
Phase: Three

Features

Baoding Zhongyi Electric Corporation is one of the leading manufacturers and suppliers of 3500 kva dry type transformer in China, featured by quality products and good price. Please rest assured to buy advanced 3500 kva dry type transformer for sale here from our factory.

 

 

Where this transformer fits:
Because the HV side reaches 35 kV, this unit is usually the main or distribution transformer of a medium-voltage network rather than a small LV supply transformer. Typical positions are 35/11 kV or 33/11 kV substations, industrial plants and mines with their own MV distribution, data centres and hospitals that must meet strict fire codes, and rail or tunnel auxiliary supplies. We build the same frame for 50 Hz or 60 Hz networks, and for indoor installation or inside a weatherproof enclosure outdoors.

 

Why choose a cast resin unit at 3.5 MVA:
At this rating you have a genuine choice between dry type and oil-immersed, and the reasons for going dry type are usually specific:

- No oil means no fire load. The unit can sit inside a building, next to switchgear, without a bund wall or fire-extinguishing oil system.
- No liquid to leak, monitor or dispose of. Routine maintenance is limited to cleaning the cooling ducts and checking connections.
- Epoxy-cast HV windings give the unit good short-circuit strength and very low partial discharge when the casting and curing process is controlled properly.
- With AN/AF cooling the same frame covers two duty points: natural convection at the nameplate rating, and a higher continuous output once the forced-air fans run.

The honest trade-off is that a cast resin unit costs more up front than an equivalent oil-immersed transformer. Customers who choose dry type are usually buying fire safety, siting flexibility, or lower life-cycle maintenance - not the lowest first price.

 

3500 KVA Dry Type Transformer

 

Core technical data
The values below are the standard design envelope. Exact losses, impedance, vector group, dimensions and weight are calculated for your voltage combination and confirmed on the general arrangement drawing we send with the quotation.

Rated power: 3500 kVA (3.5 MVA), three-phase
Primary voltage: up to 35 kV (e.g. 35, 33, 22, 20 or 11 kV class)
Secondary voltage: up to 11 kV (e.g. 11, 10.5, 6.6 or 3.3 kV)
Frequency: 50 / 60 Hz
Cooling: AN / AF
Insulation system: Class F as standard, Class H on request
Vector group: to specification (e.g. Dyn11 or YNd11, depending on neutral earthing)
Tap changer: off-circuit taps as specified (e.g. +/- 2 x 2.5%)
Standards: IEC 60076, ANSI, NEMA, UL, CSA, CE, ISO
Enclosure: IP00 open unit; IP23 to IP66 when supplied with an enclosure or kiosk
Efficiency: up to 99% at the design load point, per the loss budget agreed at order

 

3500 KVA Dry Type Transformer

Drawings you receive before production:
Because every 3.5 MVA unit is dimensioned around your site, we issue the general arrangement drawing - footprint, fixing centres, terminal and busbar positions, enclosure layout where fitted - for your approval before we cut any material. Dimensional and weight data for civil works planning comes from that drawing, not from a generic brochure figure. Outline, connection and, where requested, foundation drawings are included in the same package.

3500 KVA Dry Type Transformer

Testing before dispatch:
Each unit is routine tested in our factory to IEC 60076-11 before it leaves the floor. The routine set covers winding resistance, voltage ratio and vector group, short-circuit impedance and load loss, no-load loss and current, insulation resistance, induced overvoltage, and partial discharge - with acceptance below 10 pC at the test voltage specified by the standard. Sound level is measured on the same test. Every transformer ships with its own test report, and type tests such as lightning impulse and temperature-rise can be witnessed by your engineer or provided as reports for the design.

3500 KVA Dry Type Transformer

Documentation and certification:
Along with the test report you receive the certificates and documents applicable to the order - quality documentation for the steel, copper and epoxy materials used, the CE declaration of conformity where required, and any third-party inspection certificates arranged with your agent. If your project needs a specific certification body or an inspection during manufacturing, tell us at enquiry stage so it is included in the programme rather than added at the end

3500 KVA Dry Type Transformer

Packaging, delivery and lead time:
A unit of this size travels as project cargo. Our standard export packing protects the transformer for sea freight and for a period of outdoor storage on site - the winding is protected against moisture pick-up during transit, and the crate is built so the unit can be lifted with the beams marked on the packing. If your contract has a specific packing or preservation specification, we confirm it in writing before we commit. Lead time is quoted once the rating, voltage combination and vector group are fixed; we will give you a realistic date in the quotation rather than an optimistic one

3500 KVA Dry Type Transformer

Frequently asked questions

Q: Is 3500 kVA a standard transformer rating?
A: Not in the usual sense. Standard preference steps run from 3150 kVA to 4000 kVA, so 3500 kVA is a built-to-order rating. That works in your favour: the windings are calculated for your actual voltage, vector group and loss budget instead of you accepting whatever a standard frame gives you.

 

Q: Why would we choose dry type instead of oil-immersed at this rating?
A: Dry type removes the fire risk and the oil containment and disposal problem, which matters indoors, in urban substations and near other equipment. The first cost is higher than oil, so if your site has no restriction on oil-immersed units, tell us - we build both and will recommend the one that fits your case honestly.

 

Q: Which voltage combinations can this unit be built for?
A: The design envelope covers a primary up to 35 kV and a secondary up to 11 kV. Combinations we regularly quote include 35/11 kV, 33/11 kV, 33/6.6 kV, 20/11 kV and 11/6.6 kV, at 50 or 60 Hz, with taps and vector group set to your network.

 

Q: What does the AN/AF cooling notation mean in practice?
A: AN is the natural-air rating at which the unit runs with no fans. AF switches on forced-air cooling, which raises the continuous output the same frame can carry - typically by around 30 to 40 percent depending on the design. Many customers run AN as the base duty and use AF as the contingency for peak or N-1 conditions.

 

Q: What tests does each unit pass before shipping?
A: Every unit goes through the IEC 60076-11 routine tests: winding resistance, ratio and vector group, short-circuit impedance and load loss, no-load loss and current, insulation resistance, induced overvoltage and partial discharge (accepted below 10 pC), with sound level measured on the same test. The test report accompanies the transformer.

 

Q: Can the 3500 kVA dry type transformer be installed outdoors?
A: The open unit is IP00 and is designed for indoor or kiosk installation. For outdoor sites we supply it inside an IP23 to IP66 enclosure or a compact substation kiosk with sized ventilation and space heaters, so the cooling airflow is preserved and condensation is kept off the windings.

 

If you are sizing a 3.5 MVA dry type transformer for a specific project, send us your primary and secondary voltages, the earthing arrangement, and your site conditions. You will get the general arrangement drawing, the calculated technical data and a lead time you can plan around.